For terminal operators, refinery and chemical engineers, boiler and heater treater operators, water and wastewater utilities, and EPC specifiers who need high-integrity point-level control on pressurized vessels or bypass chambers, the Omnitrol 664F / 666F / 668F delivers rugged flanged chamber construction, factory specific-gravity calibration, and predictable switching differentials across a wide range of process fluids.
Unlike float switches or capacitance probes that can foul, drift, or require frequent field adjustment, the 66xF family uses displacer-based magnetic switching inside a forged flanged chamber that is hydrostatically tested to 1.5× its rated pressure. Each unit is tuned at the factory to the process liquid density, providing accurate alarm actuation with no field calibration required.
This design makes the series ideal for API 2350 overfill protection, separator service, heater treaters, steam systems, and pressurized tank bypass chambers, ensuring safe isolation, long service life, and reliable switching in critical industrial environments.
Integrates directly with ANSI 150/300/600 (and up to 1000-lb) flange classes, meeting plant piping standards and enabling simple maintenance isolation with standard spool pieces.
Each unit ships pre-set for your fluid SG up to 1.7, ensuring correct actuation points and minimizing field adjustment time during commissioning.
Every chamber undergoes hydrostatic testing at 1.5× maximum design pressure, providing integrity confidence and reducing HAZOP findings at startup.
Provides excellent chemical compatibility across petroleum, petrochemical, chemical, and industrial applications without requiring special material upgrades.
Weather-resistant (NEMA 4), explosion-proof/vapor-proof (Class I Groups B/C/D, Class II Groups E/F/G), and explosion-proof/rain-tight configurations available.
Certified for hazardous area classifications, ensuring compliance with plant safety standards and simplifying MOC (Management of Change) processes.
664F (4″ body), 666F (6″ body), 668F (8″ body) flanged chamber, single actuator.
Up to 1000 psig @ 500 °F (materials/options per Table G).
1.7. Factory SG set; SG affects switching differential per published table.
Carbon steel, 304 SS, 316 SS chambers; graphite displacer standard.
Weather-resistant, Explosion-proof/Vapor-proof (Cl I, Gr B/C/D; Cl II, Gr E/F/G), Explosion-proof/Rain-tight variants.
Multiple SPDT/DPDT micro options with published resistive ratings (E, G, H, M, S families).
ANSI 150/300/600 (higher classes optional). Dimensional tables published by model/pressure class.
UL & CSA (per model options).
If you have questions not covered here, please contact the Cognesense support team for assistance.
Contact Us ↵No — they are factory calibrated to your liquid’s specific gravity.
Yes — up to 1000 psig and 500 °F, depending on configuration.
The flanged design simplifies the process for maintenance isolation using standard spool piece removal. It also provides a highly robust, secure, and easily verifiable pressure seal that meets standard plant piping specifications. This is critical in high-pressure applications where integrity is paramount.
The hydrostatic proof test verifies the physical integrity of the welded chamber by subjecting it to 1.5 times the maximum rated pressure before it leaves the factory. This provides an extra layer of quality assurance and regulatory compliance, confirming the vessel integrity for high-pressure service.
Yes — the external chamber design allows head removal without tank entry.
Pressurized vessels, heater treaters, bypass chambers, separators, boilers, API 2350 overfill points.
Choose 666F/668F when handling lower-SG fluids requiring tighter switching differentials.
The Omnitrol 664F/666F/668F combines a process-piping-ready flanged chamber, factory SG calibration, tight and predictable switching differentials, and 1000 psig @ 500 °F ratings to deliver dependable level alarm and control on pressurized vessels and bypass chambers. With broad housing/switch options, UL/CSA approvals, and interface capability, it’s a low-risk, spec-clean choice for EPCs and plant engineers who want reliable performance without intrusive wetted switches or tuning hassles.